Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
SPS series systems are compact and intelligent power system with capacity from 30A to 250A, containing rectifier modules, controller module, AC connection and DC connection. In addtion, easy installation to compact size add to the success of the system
Product features:
1. 19" 1U, 3U, 4U, 5U, 6U sub-rack, easy to be embedded into all standard kinds of telecom equipment;
2. System capacity from 30A to 350A;
3. PFC technique features the system high efficiency, energy-saving and up to 0.99 power factor;
4. Intelligent fan-cooling technique brings good cooling performance, low failure rate and high reliablity;
5. Fast on-line expansion of rectifier modules enabled by hot-swap;
6. N+1 rectifier module redundancy.
Model | SPS350-48/SR4830 |
Rated Output Current | 350A |
Rated Output Voltage | 53.5Vdc (42-58 Vdc) |
Output Power | 20KW |
AC Input | |
AC Input Voltage Range | 380vac 3 phase; 220vac 1 ph tolerances: 85~300vac |
AC Input Frequency | 45Hz ~65Hz |
AC input Power Factor | ≥0.99 |
AC transfer Efficiency | ≥92% |
AC Input Lightening Protection | ClassC SPD |
DC Output | |
Output Voltage Range | 42~58 Vdc |
Current Share | ±5% |
Load Regulation | ≤0.5% |
Voltage Regulation | ≤0.1% |
Environment | |
Operating Temperature | (-20 to 50°C) (Rectifier Temp Range: -45°C to 75°C) |
Relative Humidity | 5%~95% RH, No Condensation |
Configuration | |
Slots for Rectifier Module | 7 pcs |
Rectifier Module | 5*sR4850 |
Controller | 1*CAS-03D |
DC Distribution | customizable |
Battery Breaker | 2*125A/1P |
Alarm Relay | 4pcs |
Others | |
Standard | UL60950/EN60950, EN55022, RoHS |
Communication Port | SNMP, RS232/RS485, Dry contact |
Subrack Dimension | (W*D*H) 482*330*266(6U) |
Optional | 2nd LVD, DC Lightning Protection |
Others | The LVD shall be connected between the battery/charger connection point and the load. The LVD shall disconnect the load from the battery and the rectifier if the battery voltage reached the predetermined end of discharge limit. The LVD shall automatically reconnect the load when the battery voltage recovers to an acceptable level. The LVD shall operate as follows: § Low voltage disconnect: -43.2 VDC (default) § Reconnect voltage: -48.0 VDC (default) § Voltage drops shall be considered in setting the above parameters. The LVD contactor used shall have an indication that permits visual verification of the contact position whether open or closed. |