30A 1800W 220 V AC to 48 V DC Telecom Rectifier Power Supply
30A/48VDC/1800W Rectifier System
SPS series systems are compact and intelligent power system with capacity from 30A to 250A, containing rectifier modules, controller module, AC connection and DC connection. In addtion, easy installation to compact size add to the success of the system
Product features:
1. 19" 1U, 3U, 4U, 5U, 6U sub-rack, easy to be embedded into all standard kinds of telecom equipment;
2. System capacity from 30A to 400A;
3. PFC technique features the system high efficiency, energy-saving and up to 0.99 power factor;
4. Intelligent fan-cooling technique brings good cooling performance, low failure rate and high reliablity;
5. Fast on-line expansion of rectifier modules enabled by hot-swap;
6. N+1 rectifier module redundancy.
Model | SPS30-48 /SR4815 | SPS60-48 /SR4830 | SPS90-48 /SR4830 | SPS120-48 /SR4830 | SPS200-48 /SR4850 | SPS210-48 /SR4830 | SPS350-48 /SR4850 |
Rated Output Current |
30A | 60A | 90A | 120A | 200A | 210A | 350A |
Rated Output Voltage | 53.5Vdc (42-58 Vdc) | ||||||
Output Power | 1740W | 3.6KW | 5.4KW | 7.2KW | 11.6KW | 12.6KW | 21KW |
AC Input | |||||||
AC Input Voltage Range |
176~300Vac, 1phase/3wire (@ full load) | 220/230vac 1 ph tolerances: 85~300vac 323~480vac 3ph tolerances: 208~520vac |
|||||
AC Input Frequency |
45Hz ~65Hz | ||||||
AC input Power Factor |
≥0.99 | ||||||
AC transfer Efficiency | ≥91% | ≥92% | |||||
AC Input Lightening Protection |
NA | 1*50A/2P ClassC SPD |
1*50A/2P ClassC SPD |
1*50A/2P ClassC SPD |
1*50A/2P ClassC SPD |
1*50A/2P ClassC SPD |
|
DC Output | |||||||
Output Voltage Range | 42~58 Vdc | ||||||
Current Share | ±5% | ||||||
Load Regulation | ≤0.5% | ||||||
Voltage Regulation | ≤0.1% | ||||||
Environment | |||||||
Operating Temperature | (-20 to 50°C) (Rectifier Temp Range: -45°C to 75°C) | ||||||
Relative Humidity | 5%~95% RH, No Condensation | ||||||
Configuration | |||||||
Rectifier Module | 2*SR4815 | 2*SR4830 | 3*SR4830 | 4*SR4830 | 4*SR4850 | 7*SR4830 | 7*SR4850 |
Controller | 1*CAS-03D (or CAS-02) |
1*CAS-03D (or CAS-02) | 1*CAS-03D (or CAS-02) | 1*CAS-03D (or CAS-02) | 1*CAS-03D (or CAS-02) | 1*CAS-03D (or CAS-02) | 1*CAS-03D (or CAS-02) |
DC Distribution | 1*30A | 1*60A | 4*32A/1P 4*16A/1P (customizable) | 2*63A/1P 2*32A/1P 2*16A/1P (customizable) |
2*125A/1P (customizable) | 2*125A/1P (customizable) | Customizable |
Battery Breaker | / | / | 2*63A/1P or 1*100A/1P |
2*100A/1P | 2*125A/1P | 2*125A/1P | 2*125A/1P |
Alarm Relay | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs |
Others | |||||||
Standard | UL60950/EN60950, EN55022, RoHS | ||||||
Communication Port |
SNMP, RS232/RS485, Dry contact (CAS-03D) | ||||||
Subrack Dimension (W*D*H) mm | 482*330*44 (1U) |
482*330*44 (1U) | 482*370*132 (3U) | 482*370*176 (4U) | 482*390*222 (5U) |
482*390*266 (6U) |
|
Optional | Wall-mounted | Wall-mounted | DC Lightning Protection | 2nd LVD, DC Lightning Protection |
2nd LVD, DC Lightning Protection |
2nd LVD, DC Lightning Protection |
2nd LVD; DC Lightning Protection |