Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | Whale-120K (3-3) |
Capacity(KVA) | 120 |
Input | |
Nominal Voltage | 400Vac, three phase |
Voltage Range | ±20% |
Frequency Range | 50/60Hz+5%(Auto sense) |
Power Factor | >0.92 |
Current THD | <5% |
Soft Startup | 10seconds |
Bypass | |
Nominal Voltage | 400Vac, Three phase |
Allowable Voltage | ±15% ( ±10% ~ ±25%, settable thru Touch Screen) |
Nominal Frequency | 50/60Hz (auto sense) |
Allowable Frequency | ±2% ( ±1% ~ ±5%, settable thru Touch Screen) |
Battery | |
Voltage | 480V |
Max.charge Current | 0.2 * C10 |
Output | |
Rated Power (kVA) | 120 |
Active Power (kW) | 96 |
Nominal Voltage | 400Vac, three phase/5wire (348~424, settable) |
Voltage Regulation | ±1% (static); ±5% (dynamic) |
Nominal Current (A) | 174 |
Frequency | 50/60Hz (settable) |
Frequency regulation | ±0.05% (Battery mode); ±2% (AC normal, settable from ±1% to ±5%) |
Crest ratio | 3:01 |
Wave form | True sine wave |
Overload | 110% for 5hrs, 125% for 10mintues, 150% for 1mintues |
Interface | |
Contact Relay | Dry contact relay |
Communication | RS232, LCD Display or Touch Screen |
Remote Control | Emergency power off, bypass |
Noise | 53~62dBA, 1m |
Degree of Protection | IP20 |
Ambient | Temperature: 0~40ºC, <95% no condensation |
Efficiency | >95% |
Safety & EMC | Safety: EN62040-1; EMC: EN62040-2 ClassA 73/23-93/68-89/336 EEC EN62040-3 |
Weight(kg) (Excluding battery) | 860 |
Size(H*W*D,mm) | 1070*750*1400 |