12kv Three-Phase AC 50Hz Outdoor Vaccum Circuit Breaker
General
ZW32 series outdoor high voltage vaccum circuit breaker is used in three phase power system of AC 50Hz, voltage 12~36KV to switch on/off loading current, it has function of protecting overloading and short circuit meeting the requirement of control and measurement realizing remote control and monitor and so on, it applies to protect and control distribution, industrial enterprises and frequent switching in rural network.
Application voltage levels include: 12kV, 24kV and 36kV.
Application standard: IEC62271-200
Service and Installation Conditions
Height above sea level: ≤3000m
Air temperature:-40ºC~ +50ºC
Maximum diurnal temperature difference: ≤25ºC
Relative humidity:Daily mean 95% Monthly average 90%
Maximum wind speed:≤34m/s
Earthquake intensity:< 8 degree
Icing thickness:< 10mm
Thickness of snow: < 35mm
Irradiance:<0.1W/cm2
Pollution grade:class, IV class
Installation site:No fire disaster, explosion danger, chemical corrosion and frequent strenuous vibration places
Technical Characteristics
Item |
unit |
Data |
Rated voltage |
kV |
12 |
24 |
36 |
Rated frequency |
Hz |
50/60 |
Rated current |
A |
400/630 |
Rated short-circuit withstand/ breaking current |
kA |
12.5/20 |
Rated short-circuit making current (peak) |
kA |
31.5/50 |
Rated peak withstand current |
kA |
31.5/50 |
Rated short-circuit time |
Sec |
4 |
Rated operating sequence |
|
(O)-0.3s-(CO)-180s-(CO) |
Mechanical Operations |
Times |
10000 |
Rated full load operations |
Times |
400 |
Power frequency withstand voltage (1min) |
kV |
28/32 |
50/60 |
70/80 |
Lightning impulse withstand voltage (peak) |
kV |
76/85 |
125/145 |
170/190 |
Closing time |
ms |
25-50 |
Full breaking time |
ms |
≤100 |
Arcing ime |
ms |
≤20 |
Mechanical endurance |
Time |
10000 |
Rated input power of charging motor |
W |
40 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC200, 110, 24 |
DC220, 110, 24 |
Charging time at rated voltage |
s |
≤10 |
Over-current release |
Rated current |
A |
50 |
Accuracy of tripping current |
% |
±10 |
Mechanical endurance |
time |
10000 |