Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model Name | 10KL 3-3 | 10KS 3-3 | 20KL 3-3 | 20KS 3-3 | 30KL 3-3 | 30KS 3-3 | ||||||
Input | ||||||||||||
Grid System | 3 Phases + Neutral + Ground | |||||||||||
Rated Voltage | 200/208/220VAC (Line-Line) | |||||||||||
Rated Frequency | 50/60Hz | |||||||||||
Voltage Range | 187~260Vac (Line-Line),full load; 125V~187Vac (Line-Line),load decreases linearly according to the min phase voltage |
167~260Vac (Line-Line),full load; 125V~167Vac (Line-Line),load decreases linearly according to the min phase voltage |
||||||||||
Frequency Range | 40Hz~70Hz | |||||||||||
Power Factor | >0.99 | |||||||||||
Current THDi | <5% (linear load) | <4% (linear load) | ||||||||||
Bypass Input | ||||||||||||
Rated Voltage | 200/208/220VAC (Line-Line) | |||||||||||
Rated Frequency | 50/60Hz | |||||||||||
Voltage Range | Selectable, default -20%~+15%; Upper limit: +10%, +15%, +20%, +25%; Lower limit: -10%, -15%, -20%, -30%, -40% | |||||||||||
Frequency Range | Selectable, ±1Hz, ±3Hz, ±5Hz | |||||||||||
Overload | 125% Long term operation; 125%~130% for 10min; 130%~150% for 1min; | 110% Long term operation; 110%~ 125% for 1min; 125%~150% for 30s | ||||||||||
Output | ||||||||||||
Rated Inverter Voltage | 200/208/220VAC (Line-Line) | |||||||||||
Rated Frequency | 50/60Hz | |||||||||||
Power Factor | 1 | 0.9 | ||||||||||
Voltage Precision | ±1.5%(0-100% linear load) | |||||||||||
Transient Response | <5% for step load (20% - 80% -20%) | |||||||||||
Transient recovery | < 30ms for step load (20% - 100% -20%) | |||||||||||
Output Voltage THDu | <1.5% (linear load); <6% (non-linear load) according to IEC/EN62040-3 | |||||||||||
Inverter Overload | <110%, 10min; 110%~125%,1min; 125%~150%,30s; >150% , 200ms | <110%, 60min; 110%~125%,10min; 125%~150%,1min; | ||||||||||
Frequency Regulation | 50/60Hz±0.1% | |||||||||||
Synchronized Range | Settable, ±0.5Hz ~ ±5Hz, default ±3Hz | |||||||||||
Synchronized Slew Rate | Settable, 0.5Hz/S ~ 3Hz/s, default 0.5Hz/s | |||||||||||
Battery And Charger | ||||||||||||
Rate Voltage | ±120VDC | |||||||||||
Charger Voltage Precision | 1% | |||||||||||
Charger Power | max=20% System Power | |||||||||||
Efficiency | ||||||||||||
Normal Operation | 93%max | 94%max | ||||||||||
Battery Operation | 92.5%max | 93%max | ||||||||||
System | ||||||||||||
Display | LCD+LED | |||||||||||
Interface | Standard: RS232, RS485; Option: SNMP, Dry Contact, Parallel kit,Battery cold start | |||||||||||
Environmental | ||||||||||||
Operation Temperature | 0-40ºC | |||||||||||
Storage Temperature | -40 ~ 70 ºC | |||||||||||
Relative Humidity | 0-95% (non-comdensing) | |||||||||||
Noise (1 meter) | 58dB @ 100% load, 52dB @ 45% load | 70dB @ 100% load, 62dB @ 45% load | ||||||||||
Physical | ||||||||||||
Size (D*W*Hmm) | 250*660*530 | 250*840*715 | 250*950*770 | 500*840*1400 | 250*950*770 | 500*840*1400 | ||||||
Net Weight (KG) | 31 | 51.5(w/o battery) | 64 | 140(w/o battery) | 64 | 140(w/o battery) |
Model Name | 60K 3-3 | 90K 3-3 | 120K 3-3 | 150K 3-3 | 180K 3-3 | 300K 3-3 | ||||||
Input | ||||||||||||
Grid System | 3 Phases + Neutral + Ground | |||||||||||
Rated Voltage | 200/208/220VAC (Line-Line) | |||||||||||
Rated Frequency | 50/60Hz | |||||||||||
Voltage Range | 166~261Vac (Line-Line),full load; 125V~166Vac (Line-Line),load decrease linearly according to the min phase voltage | |||||||||||
Frequency Range | 40Hz~70Hz | |||||||||||
Power Factor | >0.99 | |||||||||||
Current THDi | <3% (full Linear Load) | |||||||||||
Bypass Input | ||||||||||||
Rated Voltage | 200/208/220VAC (Line-Line) | |||||||||||
Rated Frequency | 50/60Hz | |||||||||||
Voltage Range | Selectable, default -20%~+15%; Upper limit: +10%, +15%, +20%, +25%; Lower limit: -10%, -15%, -20%, -30%, -40% | |||||||||||
Frequency Range | Selectable, ±1Hz, ±3Hz, ±5Hz | |||||||||||
Overload | 125%, long time operation; 125%< load <130%, last for more than 10 minutes; 130%<load<150%,last for more than 1 minutes; >1000%, last for more than 100ms | 110% Long term operation; 110%~125% for 5min; 125%~ 150% for 1min; 150%~400% for 1s; >400% ,less than 200ms | ||||||||||
Output | ||||||||||||
Rated Inverter Voltage | 200/208/220VAC (Line-Line) | |||||||||||
Rated Frequency | 50/60Hz | |||||||||||
Power Factor | 0.9 | |||||||||||
Voltage Precision | Balance load: ±1%; Unbalance load: ±1.5% | |||||||||||
Transient Response | <5% for step load (20% - 80% -20%) | |||||||||||
Transient recovery | < 30ms for step load (0% - 100% -0%) | |||||||||||
Output Voltage THDu | <1.5% from 0% to 100% linear load; <6% full non-linear load according to IEC/EN62040-3 | |||||||||||
Inverter Overload | <110%, 60min; 110%~125%,10min; 125%~150%,1min; >150%,200ms | |||||||||||
Frequency Regulation | 50/60Hz±0.01% | |||||||||||
Synchronized Range | Settable, ±0.5Hz ~ ±5Hz, default ±3Hz | |||||||||||
Synchronized Slew Rate | Settable, 0.5Hz/S ~ 3Hz/S, default 0.5Hz/S | |||||||||||
Battery And Charger | ||||||||||||
Rate Voltage | ±120VDC | |||||||||||
Charger Voltage Precision | 1% | |||||||||||
Charger Power | max=20% System Power | |||||||||||
Efficiency | ||||||||||||
Normal Operation | >93% | |||||||||||
Battery Operation | >93% | |||||||||||
System | ||||||||||||
Display | LED + LCD + touch screen | |||||||||||
Interface | Standard:RS232, RS485, USB,Dry contact(Programmable ) | |||||||||||
Environmental | ||||||||||||
Operation Temperature | 0-40ºC | |||||||||||
Storage Temperature | -40 ~ 70 ºC | |||||||||||
Relative Humidity | 0-95% (non-comdensing) | |||||||||||
Noise (1 meter) | 65dB @ 100% load, 62dB @ 45% load | |||||||||||
Altitude | <1000m, Load derated 1% per 100m From 1000 ~ 2000m | |||||||||||
Physical | ||||||||||||
Size (D*W*Hmm) | 600*980*1150 | 650*960*2000 | 650*960*1600 | 650*960*2000 | 650*960*2000 | 1300*1100*2000 | ||||||
Net Weight (KG) | 210 | 305 | 350 | 445 | 490 | 900 |