Customization: | Available |
---|---|
Application: | Home Theater |
Nature of Source Flow: | Active Inverter |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | ND110-1101 | ND110-1102 | ND110-1103 | ND110-1105 | |
DC Input |
Rated Input Voltage | 110 VDC | |||
Rated Input Current | 9.09A | 19A | 27A | 45A | |
DC Input Voltage Range | 88~132Vdc | ||||
Bypass Utility Input |
AC Input Voltage | 110Vac±20%, 50/60Hz | |||
Rated Input Current | 4.5A | 9A | 13.5A | 56A | |
Bypass Transfer Time | ≤4 ms | ||||
AC Output |
Rated Capacity | 1KVA | 2KVA | 3KVA | 5KVA |
Rated Output Power | 0.8KW | 1.6KW | 2.4KW | 4KW | |
Rated Output Voltage and Frequency | 110VAC, 50Hz/60Hz | ||||
Rated Output Current | 9A | 18A | 27A | 56A | |
Output Voltage Regulation | 110Vac±2% | ||||
Output Frequency Regulation | 50/60Hz±1% | ||||
THD | ≤3% | ||||
Dynamic Response (Load 0←→100%) | 5% | ||||
Power Factor | 0.8 | ||||
Overload | 110-150% 30s,inverter shut off and transfer to bypass; >150% immediately shut off and transfer to bypass. | ||||
Crest Factor | 3:01 | ||||
Efficiency at Rated Load | 90% | ||||
Environment |
Insulation Strength (Between Input & Output) | 1500VAC, 1min | |||
Noise (1m) | ≤50dB | ||||
Temperature | -10ºC~+50ºC | ||||
Humidity | 0~90%, no condensation | ||||
Altitude (m) | ≤2000 | ||||
Physical |
Rack Type (W* D * H, mm) | 440×450×177 | 440×450×177 | 440×500×221.5 | |
Tower Type (W* D * H, mm) | 200*480*490 | 210*612*540 | 305*585*865 | ||
Rack Type Weight (kg) | 30 | 31 | 32 | 46 | |
Tower Type Weight (kg) | 32 | 33 | 34 | 65 | |
Protection |
DC input reversely protection, DC input under voltage,over voltage, overload, short circuit, over temperature |