Customization: | Available |
---|---|
Certification: | ISO9001, CE |
Output Power: | >1000W |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | ND110-1080 | ||||
DC input | |||||
Rated Input Voltage | 110 VDC | ||||
Rated Input Current | 72A | ||||
DC Input Voltage Range | 88~132Vdc | ||||
Bypass Utility Input | |||||
AC Input Voltage | 220Vac±20%, 50/60Hz ±10% | ||||
Rated Input Current | 36A | ||||
Bypass Transfer Time | ≤4 ms | ||||
AC Output | |||||
Rated Capacity | 8KVA | ||||
Rated Output Power | 6.4KW | ||||
Rated Output Voltage and Frequency | 220VAC, 50/60Hz | ||||
Rated Output Current | 36A | ||||
Output Voltage Regulation | 220Vac±2% | ||||
Output Frequency Regulation | 50/60Hz ±1% | ||||
THD | ≤3% | ||||
Dynamic Response (Load 0←→100%) |
5% | ||||
Power Factor | 0.8 | ||||
Overload | 110-150% 30s,inverter shut off and transfer to bypass; >150% immediately shut off and transfer to bypass. |
||||
Crest Factor | 3:01 | ||||
Efficiency at Rated Load | 90% | ||||
Environment | |||||
Insulation Strength (Between Input & Output) |
1500VAC, 1min | ||||
Noise (1m) | ≤50dB | ||||
Temperature | -10ºC~+50ºC | ||||
Humidity | 0~90%, no condensation | ||||
Altitude (m) | ≤2000 | ||||
Physical | |||||
Size (W* D * H, mm) | 343*630*700 | ||||
Type | Tower Type | ||||
Protection | DC input reversely protection, DC input under voltage, over voltage, overload, short circuit, over temperature |