Customization: | Available |
---|---|
Application: | PlayStation |
Nature of Source Flow: | Passive inverter |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | ND 220 | ND220 | ND220 | ND220 | ND220 | ND220 | ND220 | ND220 | ND 220 | ND 220 | |
-1010 | -1020 | -1030 | -1050 | -1100 | -1120 | -1150 | -1200 | -1300 | -1400 | ||
DC input | Rated DC input voltage (VDC) | 220 | |||||||||
Rated DC input current (A) | 5 | 10 | 16.3 | 25 | 49 | 59 | 75 | 99 | 148 | 198 | |
DC input voltage range (VDC) | 180~300Vdc | ||||||||||
Bypass | Utility AC input voltage (VAC) | 220Vac±20%, 50Hz±10% | |||||||||
Utility | Rated AC input voltage (A) | 4.5 | 9 | 13.5 | 22.7 | 45 | 54.5 | 68.5 | 91 | 136 | 182 |
Input | Bypass transfer time (ms) | ≤4 | |||||||||
AC output | Rated capacity (KVA) | 1 | 2 | 3 | 5 | 10 | 12 | 15 | 20 | 30 | 40 |
Rated output power (KW) | 0.8 | 1.6 | 2.4 | 4 | 8 | 10 | 12 | 16 | 24 | 32 | |
Rated output voltage and frequency | 220VAC, 50HZ | ||||||||||
Rated output current (A) | 3.65 | 7.3 | 11 | 18.2 | 36.4 | 45.5 | 54.5 | 72.8 | 109 | 145 | |
Output voltage regulation (Vac) | 220±2% | ||||||||||
Output frequency regulation(Hz) | 50±1% | ||||||||||
THD | ≤3% | ||||||||||
Dynamic response (load 0←→100%) | 5% | ||||||||||
Power factor | 0.8 | ||||||||||
Overload | 150%,60s | ||||||||||
Crest factor | 3:01 | ||||||||||
Efficiency at rated load | 90% | 90% | |||||||||
Environment | Insulation strength (between input & output) | 1500VAC, 1min | |||||||||
Noise (1m) | ≤50dB | ||||||||||
Temperature | -10ºC~+50ºC | ||||||||||
Humidity | 0~90%, no condensation | ||||||||||
Altitude (m) | ≤2000 | ||||||||||
Sizes | Rack tye (W* D * H, mm) | 440×450×177 | 440×450×177 | 440×450×177 | 440×500×221.5 | 330×640×885 | 380×680×935 | 410×720×935 | 490×985×1205 | ||
Weight () | 30 | 50 | 55 | 70 | 122 | 135 | 158 | 175 | 270 | 450 | |
Protection | DC input reversely protection, DC input under voltage, overload, short circuit, over temperature |