Customization: | Available |
---|---|
Nature of Source Flow: | Active Inverter |
Phase: | Single |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
120VDC Input 120VAC Output Power Inverter
Introduction:
ND series are specially designed for railway and electric power industry. Their latest advanced technology suits all
critical situations Which are sensitive to power interference and need stable, reliable, clean and uninterruptible true
sine wave power supply.
Main Features:
Model | ND120- 1101 |
ND120- 1102 |
ND120- 1103 |
ND120- 1105 |
ND120- 1106 |
ND120- 1110 |
ND120- 1115 |
ND120- 1120 |
ND120- 1125 |
ND120- 1130 |
||||
DC input | ||||||||||||||
Rated DC Input Voltage | 120V | |||||||||||||
Rated Input Current | 7A | 15A | 23A | 39A | 47A | 78A | 117A | 156A | 196A | 235A | ||||
DC Input Voltage Range | 100~ 150Vdc | |||||||||||||
Bypass Utility Input | ||||||||||||||
AC Input Voltage | 120Vac±20%, 50/60Hz±10% | |||||||||||||
Rated Input Current | 8A | 16.6A | 25A | 41.6A | 50A | 83A | 125A | 166A | 208A | 250A | ||||
Bypass Transfer Time | ≤4 ms | |||||||||||||
AC Output | ||||||||||||||
Rated Capacity | 1KVA | 2KVA | 3KVA | 5KVA | 6KVA | 10KVA | 15KVA | 20KVA | 25KVA | 30KVA | ||||
Rated Output Power | 0.8KW | 1.6KW | 2.4KW | 4KW | 4.8KW | 8KW | 12KW | 16KW | 20KW | 24KW | ||||
Rated Output Voltage and Frequency | 120VAC, 50HZ | |||||||||||||
Rated Output Current | 8A | 16.6A | 25A | 41.6A | 50A | 83A | 125A | 166A | 208A | 250A | ||||
Output Voltage Regulation | 120Vac±2% | |||||||||||||
Output Frequency Regulation | 50/60Hz ±1% | |||||||||||||
THD | ≤3% | |||||||||||||
Dynamic Response | 5% (Load 0←→ 100%) | |||||||||||||
Power Factor | 0.8 | |||||||||||||
Overload | 110-150% 30s ,inverter shut off and transfer to bypass; >150% immediately shut off and transfer to bypass. |
|||||||||||||
Crest Factor | 3:01 | |||||||||||||
Efficiency at Rated Load | 90% | |||||||||||||
Environment | ||||||||||||||
Insulation Strength (Between Input & Output) |
1500VAC, 1min | |||||||||||||
Noise (1m) | ≤50dB | |||||||||||||
Temperature | -10ºC~+50ºC | |||||||||||||
Humidity | 0~90%, no condensation | |||||||||||||
Altitude (m) | ≤2000 | |||||||||||||
Communication Interface | Dry Relay | |||||||||||||
Cooling Method | Forced air-cooling with temperature control | |||||||||||||
Size (W* D * H, mm) | 440×450×177 | 440×500×221 | 305*585*865 | 409*800*1050 | 555*740*1220 | |||||||||
Type | Rack Type | Tower Type | ||||||||||||
Protection | DC input reversely protection, DC input under voltage,over voltage, over current overload, short circuit, over temperature |