Phase: | Three Phase |
---|---|
Type: | On-line |
Protection: | Overvoltage |
Application: | Industry |
Classification: | Lighting/Power |
Standby Time: | Long-acting Machine |
Customization: |
---|
Suppliers with verified business licenses
Capacity | 10KVA | 15KVA | 20KVA | 30KVA | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA |
Main Input | |||||||||||||||
Input voltage | 380V/400V/415V(line to line), 50/60Hz | ||||||||||||||
Input connection | 3Ph+N+PE | ||||||||||||||
Power factor | >0.99 | ||||||||||||||
Input voltage window | +25%~-20%, full load | ||||||||||||||
-20%~-40%, power derating between 100% to 70% | |||||||||||||||
Frequency window | 40-70HZ | ||||||||||||||
Bypass input | |||||||||||||||
Bypass voltage | 380V/400V/415V | ||||||||||||||
Bypass voltage window | +15%--20%, full load | ||||||||||||||
Frequency window | ±5Hz | ||||||||||||||
Battery | |||||||||||||||
Battery voltage | ±240VDC | ||||||||||||||
Charger power | 20%*Power | ||||||||||||||
Charger voltage precision | 1% | ||||||||||||||
Output | |||||||||||||||
Voltage precision | 1% (balance load),1.5% (unbalance load) | ||||||||||||||
Output voltage transient | 5%(0~100% load step) | ||||||||||||||
Voltage THD(Total Harmonic Distortion) | THD<1%(linear load),THD<5%(nonlinear load) | ||||||||||||||
Power factor | 0.8 | ||||||||||||||
Frequency tracking range | 50/60Hz±3Hz, adjustable | ||||||||||||||
Frequency precision (free running) | ±0.02% | ||||||||||||||
Phase tolerance | 120°±0.5° (balance and unalance load) | ||||||||||||||
Voltage unbalance degree (100% unbalance load) | ±1% | ||||||||||||||
Frequency tracking speed | 0.5Hz/s to 5Hz/s, adjustable | ||||||||||||||
Crest factor | 3:1 | ||||||||||||||
Overload capabiltiy | 102% long time operation | ||||||||||||||
110%, transfer to bypass after 1hour | |||||||||||||||
125%, transfer to bypass after 10 minutes | |||||||||||||||
150%, transfer to bypass after 1 minute | |||||||||||||||
>150%, transfer to bypass after 200ms | |||||||||||||||
Bypass overload capability | 125%, long time operation | ||||||||||||||
125%< load <130%, last for more than 1 hour | |||||||||||||||
130%<load<150%,last for more than 6 minutes | |||||||||||||||
>1000%, last for more than 100ms | |||||||||||||||
System | |||||||||||||||
System efficiency | Normal mode: 95% | ||||||||||||||
ECO mode: 99% | |||||||||||||||
Battery mode efficiency | 95% | ||||||||||||||
Battery configuration | 12V, 40PCS (36~44pcs acceptable) | ||||||||||||||
Display | LCD+LED, keyboard | LCD+LED, Touch screen and keyboard | |||||||||||||
EMI | IEC62040-2 | ||||||||||||||
EMS | IEC61000-4-2(ESD) | ||||||||||||||
IEC61000-4-3(RS) | |||||||||||||||
IEC61000-4-4 (EFT) | |||||||||||||||
IEC61000-4-5 (Surge) | |||||||||||||||
Insulation resistance | >2M (500VDC) | ||||||||||||||
Dielectric strengh | (input,output to PE)2820Vdc, leakage current lower than 3.5mA, no flashover in 1 minute | ||||||||||||||
Surge protection | Comply with IEC60664-1 class IV, endure surge of 1.2/50us + 8/20us higher than 6KV/3KA | ||||||||||||||
IP class | IP20 | ||||||||||||||
Interface (Communication Ports ) | RS232,RS485,Dry contacts,SNMP card,EPO,Generator interface | ||||||||||||||
Installation/Connection | Top or bottom cable connection | ||||||||||||||
Operation temperature | 0-40 ºC | ||||||||||||||
Relative humidity | 0-90% (non-comdensing) | ||||||||||||||
Noise(dB) | <55dB | ||||||||||||||
Weight(KG) | 65 | 68 | 68 | 80 | 43 | 46 | 46 | 60 | 182 | 204 | 226 | 270 | 292 | 358 | 380 |
Dimension(W*D*H)(mm) | 540*690*1100 (Internal battery) |
280*730*668 | 320*781*788 | 600*855*1350 | 600*855*1600 | 600*855*2000 |
Suppliers with verified business licenses