Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | Line Interactive |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model Name | 0.5KL | 0.5KS | 1KL | 1KS | 1.5KL | 1.5KS | 2KL | 2KS | 3KL | 3KS | 6KL | 8KL | 10KS | |
Capacity (VA / Watt) | 500VA/300W | 1kVA/700W | 1.5kVA/1050W | 1.5kVA/900W | 2kVA/1.4kW | 3kVA/ 2.1kW | 6kVA/4.2kW | 8kVA/5.6kW | 10kVA/ 7kW | |||||
Overview | ||||||||||||||
Power Factor | 0.6 | 0.7 | 0.6 | 0.7 | ||||||||||
Outlook | Tower | Tower or Rack (3U) | Tower | |||||||||||
Waveform | True Sine Wave | |||||||||||||
Input | ||||||||||||||
Nominal Voltage | 230V | |||||||||||||
Voltage Range | 150-275Vac | 154V~299V | ||||||||||||
Frequency Range | 45HZ~60HZ | |||||||||||||
Output | ||||||||||||||
Nominal Voltage | 230VAC | |||||||||||||
Voltage Range | AC Mode: 200V~253V; Batt Mode:230V±6% | AC Mode: 200V~253V; Batt Mode: 230V±3% | ||||||||||||
Frequency Range | (50/60Hz)±0.5% (Autosense) | |||||||||||||
Overload Protection | (AC Mode) >120% --- 1min S/D; (Batt Mode) >120% ---15Sec S/D, >140%---immed UPS Off. |
(AC Mode) Alarm (Fuse or C.B Protection); (Batt Mode) 110~140%->20Sec, >140%->5Sec. |
||||||||||||
Battery | ||||||||||||||
Voltage | 12VDC | 24VDC | 36VDC | 24VDC | 48VDC | |||||||||
Quantity | N/C | 12v7ah*1 | N/C | 12v7ah*2 | N/C | 12v9ah*2 | N/C | 12v7ah*4 | N/C | 12v12ah*4 | N/C | N/C | 12v12ah*12 | |
Cold Start (DC Start) | Yes | |||||||||||||
Hot Replacement | Yes | |||||||||||||
Max Charger Current | 10A | 1.5A | 15A | 1.5A | 20A | 1.5A | 20A | 2A | 20A | 2A | 30A | 30A | 5A | |
Overcharge Protection | Yes | |||||||||||||
Charging When UPS off | Yes | |||||||||||||
Communication | ||||||||||||||
Data Line Network Protection(Optional) |
N/C | RJ45 (1 in/1 out) | N/C | |||||||||||
Intelligent Interface | RS232 OR USB | |||||||||||||
SNMP slot | Optional | |||||||||||||
Display | ||||||||||||||
LED Status | Line,Batt Mode /Charging, Overload, Fault | Line,Batt Mode/Charging, Overload / Fault; Batt Capacity; Load Size |
Line/Batt Mode, AVR, Batt Capacity: Load Size; Overload, Fault, Batt Replacement |
|||||||||||
LCD (OPTIONAL) | O/P Voltage, Input Voltage and Frequency; Battery Capacity; Load Size. |
O/P Voltage, Input Voltage and Frequency; Batt Capacity; Load Size.Mode |
||||||||||||
Safety&EMC Approved | CE/TUV/FCC | |||||||||||||
Physical | ||||||||||||||
Dimension (D*W*Hmm) |
360*122*193 | 383*140*212 | 435*430*135 | 440*190*330 | 508*300*792 | |||||||||
Net Weight(KG) | 6.5 | 8 | 9.5 | 11 | 13 | 12 | 18 | 28 | 21.5 | 34.5 | 38.25 | 60 | 102 | |
Ambient | ||||||||||||||
Temperature | 0~45° | |||||||||||||
Related Humidity | 10%~90%(no condensation) | |||||||||||||
Altitude | 1500m |