Dragon-I series use advanced true double conversion on-line topology ideal for resolving all issues on power supply. The expanded input range increases battery life by eliminating unnecessary discharge & recharge. Runtime can also be expanded with scalable external battery pack providing worry free for long blackout.
Base on the Dragon-I, Dragon-II ups are developed with new functions like: EPO, higher output power factor (up to 0.8) and etc.
Main features
1) True online double conversion technology with microprocessor & DSP control
2) Wide input voltage range
3) Advanced PFC technology with input power factor approaching to 1
4) Fully protection: Lightning and surge protection, EMI/RFI filter, over voltage, short circuit, overload and etc
5) Enable to extend runtime with scalable external battery pack
6) Maintenance bypass switch for 6K~20K
7) RS-232 /USB communication port
8) Smart Snmp card slot available
9) N+X parallel redundancy and capacity expansion for 6K~10K
Dragon-II Particular:
1) Emergency Power Off (EPO):
2) Output power factor up to 0.8
3) Large blue LCD Display
4) Battery voltage (192V or 240V) can be selected on User demands.
Model |
1K (L) |
2K(L) |
3K (L) |
6K (L) |
10 K(L) |
10 KL 3-1 |
Capacity |
Capacity |
1KVA/800W |
2KVA/1600W |
3KVA/2400W |
6KVA/4800W |
10KVA/8000W |
10KVA/8000W |
Nominal Voltage |
208/220/230/240VAC Single phase 2 wire+G |
380/400/415VAC 3phase 4wire+G |
Nominal Frequency |
50/60HZ (auto sensing) |
Input |
Voltage Range |
115~300VAC |
120~275VAC |
208~476VAC |
Frequency Range |
50HZ: (46~54HZ); 60HZ:(56HZ~64HZ) |
Power Factor |
> 0.98 |
0.99 |
Output |
Voltage Precision |
208/220/230/240X 1 ( ±2% ) VAC |
Frequency Precision |
50/60Hz ±0.05Hz |
Power Factor |
0.8 |
Harmonic Distortion |
Linear load<3% Non-linear<6% |
Overload Capacity |
load > 110% for 47s; load > 150% for 25s; load > 200% for 300ms; |
105% < load ≤125% for 60s; 125% < load ≤150% for 30s; load >150% for 0.5s. |
Current Crest Ratio |
3:1 |
Transfer time |
0 ms(AC mode↔DC mode);(AC mode↔Bypass<4ms) |
Battery |
DC Voltage |
36VDC |
72VDC |
96VDC |
192 or 240VDC(Optional) |
Recharge Time |
5 hours to 90%(it means standard model which battery inside UPS) |
Panel Display |
LCD |
UPS status, input/output voltage and frequency, battery voltage, capacity, load temperature, history records, adjust voltage, ECO mode |
Communication port |
RS232, SNMP Card(Optional),USB port(Optional) |
Working Environment |
Temperature |
0 ºC~ 40 ºC |
Relative Humidity |
0 ~ 95% ( Non-condensing ) |
Elevation |
1500 m |
Noise Level |
< 45dB |
< 50dB |
Physics Characteristic |
Weight ( Kg ) |
N.W |
12(6.5) |
23(10.5) |
31.5(14) |
57(18) |
67.5(20) |
20 |
Dimension:(WxDxH) |
145X355X220 |
190X383X318 |
190X433X318 |
248X500X616 (248X500X460 ) |
248X500X672 |