Home » Offer List » UPS » 60kVA Online 220vac UPS
Offer Details
60kVA Online 220vac UPS
| Offer Type: | ![]() |
|---|---|
| Offer Category: | Electrical & Electronics >Power Supply & Distribution > UPS |
| Offer Post Time: | May 18, 2012 |
| Expiration Date: | Dec 16, 2012 |
Details:
6 to 60kVA
380Vac/3phase input
220Vac/1phase output
1. Advance IGBT inverted technology
2. Multiple CPU intelligent control
3. Multiple protection function of over-voltage, short circuit, over-temperature
4. LCD front panel
5. Speical industrial design to ensure the safety in worse environment
6. Reliable, filtering and stable sine wave output
7. Cold start with DC function, unmanned function
8. Online double-conversion, with output isolation transformer
| PQZ2K~20K (1phase in and 1phase out) | ||||||||||
| Mode: | PQZ1K | PQZ2K | PQZ3K | PQZ6K | PQZ10K | PQZ15K | PQZ20K | |||
| Capacity (VA/W) | 1K/0.8K | 2K/1.6K | 3K/2.4K | 6K/4.8K | 10K/8K | 15K/12K | 20K/16K | |||
| Input Voltage | Single phase with two Lines+ground wire, 230V± 25% | |||||||||
| Noise | ≤ 52dB(distance 1m) | ≤ 60dB(distance 1m) | ||||||||
| Size | 530× 264× 592 | 630× 343× 700 | ||||||||
| (D× W× H, mm) | ||||||||||
| Weight (Kg) (w/o battery) | 30 | 65 | 70 | 80 | 145 | 160 | 180 | |||
| PQZ6K3~60K3 (Three- in and single- out) | ||||||||||
| Mode: | PQZ6K3 | PQZ10K3 | PQZ15K3 | PQZ20K3 | PQZ30K3 | PQZ40K3 | PQZ50K3 | PQZ60K3 | ||
| Capacity (VA/W) | 6K/4.8K | 10K/8K | 15K/12K | 20K/16K | 30K/24K | 40K/32K | 50K/40 | 60K/48K | ||
| Input Voltage | Three phase with four Lines+ground wire, 380V± 25% | |||||||||
| Noise | ≤ 60dB(distance 1m) | ≤ 65dB(distance 1m) | ||||||||
| Size | 620× 343× 995 | 650× 700× 1510 | ||||||||
| (D× W× H, mm) | ||||||||||
| Weight(Kg) (w/o battery) | 130 | 165 | 180 | 220 | 400 | 450 | 530 | 620 | ||
| Common parameters | ||||||||||
| Input | Frequency | 50Hz /60Hz ± 10% | ||||||||
| Power factor | ≥ 0.95 | |||||||||
| Output | Voltage | 220V± 0.5% | ||||||||
| Voltage regulation | Stable ± 1%, dynamic ± 2%, (< 20ms for 0-100%load change) | |||||||||
| Frequency stabilization | 50Hz /60Hz ± 0.5% (Battery Mode) | |||||||||
| Frequency slow rate | < 1Hz / second | |||||||||
| Transient response | ± 0.4% (100% instant load fluctuation) | |||||||||
| THD | < 3% for linear load; < 5% for non-linear load | |||||||||
| Overload | 110%~150% for 10seconds; > 150% for 1second | |||||||||
| Wave form | True sine wave | |||||||||
| Efficiency | Input AC to output AC | > 90% | ||||||||
| Transfer time | AC mains fails and/or restores | 0second | ||||||||
| UPS to BYPASS | < 4 ms | |||||||||
| Battery | Voltage | 192V | ||||||||
| Charge time | 8 hrs’ recharge to 90% capacity | |||||||||
| Alarm | Battery discharge | Beeps once every 4 seconds when battery discharge | ||||||||
| Beeps once every 1 second when battery low. | ||||||||||
| Beeps continuously when battery discharge stop | ||||||||||
| UPS fault | Beeps continuously | |||||||||
| Protection | Battery low | Auto shutdown when battery low without fuse protection. | ||||||||
| Overload | 110~150% overload for 10 seconds, then auto jumps to BYPASS; Auto resumes when overload removed | |||||||||
| Over temperature | Auto jumps to BYPASS when UPS internal temperature > 85° C | |||||||||
| Output short circuit | Current limits, auto shutdown, no fuse switch protection. | |||||||||
| UPS fault | Auto jumps to BYPASS | |||||||||
| Noise Filter< 0} | 10~10KHz at 40 db; 100KHz~100MHz at 70 db | |||||||||
| Display | LCD | Input and output voltage, frequency; battery voltage and output power (%), etc | ||||||||
| LED (BLV) | LED (BLV) turns on when battery voltage low. | |||||||||
| Ambient | Temperature | 0~40degC | ||||||||
| Relative humidity | 10%~90% (No condensation) | |||||||||
| Altitude | 1500 meters | |||||||||
Inquiry Basket (